OEM Modules  
 
 


Family of input and output modules that can be used in a RTU model RTU587 or as OEM modules for telecontrol and automation applications.
The family includes digital and analogical input and outputs modules.
They are designed to be used in sub stations of electrical networks.

CHARACTERISTICS

  • OEM Modules input/output modules for use in automation and telecontrol of electrical networks.
  • Suitable to be used in electrical networks, in stations, sub stations or power plants.
  • Can be mounted in normal racks.
  • Presentation includes two parts of easy connection and disconnection; the base, passive with that allows the mechanical assembling and exterior connections and the active part that connects on the base that contains the whole active circuit.
  • Digital input card TED32B, sincronizable for GPS.
  • Modbus protocol
  • Digital outputs card TSR8 and TSR16 support a command sequence with two stages, preselection and action.
 
 

 
 
     
  32 digital input card, TED32B

28 kb  
  Protocol converter, IF-IRIG 38 kb  
  32 digital input card isolated with communication Modbus, TED32M 76 kb  
  8 digital output card, TSR8 103 kb  
  16 digital output card, TSR16 26 kb  
  8 isolated analog input card, TEA8A 128 kb  
  4 analog output card, TSA4 229 kb  
  8 analog input card for PT100, TPT8 85 kb  
 

 
 
 
 

Digital input card, TED32B

Brochure
28 kb  

  • Function: Acquire signals coming from an electrical system, to preprocess and transmit them to the CPU of the RTU.
  • Inputs:
    32, passive digital, isolated
    Voltage: 48, 110, 125 or 220 Vdc
  • Communications:
    Serial port RS485
    Time synchronization from CPU or GPS
  • With the CNVIRIG422 accessory, it can synchronize time with 1 ms of resolution directly from a signal of GPS type IRIG-B.
  • Power supply: 19 to 28 Vdc
    Input current: 100 mA

 



TED32
 
 
 
 
 

Protocol converter , IF-IRIG

Brochure 38 kb  
 

MUXFO
  • Function: Protocol conversion between an IRIG-B data source and the IRIG synchronisation module of the RTUQM system..
  • Inputs and outputs:
    IRIG-B side, terminals: IRIG+ and IRIG-
    RS232 side, terminals: TX, 1PPS, GND
  • Power supply
    Voltage: 24 Vdc ± 20 %
    Power consumption: 75 mA @ 24 Vdc
    Terminals: 0 V, 24 V
 
 

 
 

32 digital input card isolated with communication Modbus, TED32M

Brochure
76 kb  

  • Function: Acquire digital signals, to preprocess and transmit them to the master Modbus.
  • Inputs:
    32, passive digital, isolated
    Voltage: 48, 110, 125 or 220 Vdc
  • Communications:
    Serial port RS485
  • Modbus protocol slave RTU.
  • Power supply: 19 to 28 Vdc
    Input current: 100 mA

 



TED32
 

 
 

Digital output card, TSR8

Brochure 103 kb  
 

CONV232FOR
  • Function: Convert the digital signals coming from the CPU into amplified and isolated digital signals.
  • Outputs: 8, by relay
    Contacts rated: 5 A @ 125 Vdc
  • Communications:
    Serial port RS485
  • Power supply: 19 to 28 Vdc
    Static input current: 100 mA
 

 
 

Digital output card, TSR16

Brochure
 26 kb  

  • Function: Convert the digital signals coming from the CPU into amplified and isolated digital signals.
  • Outputs: 16, by relay
    Contacts rated: 5 A @ 125 Vdc
  • Communications:
    Port RS485
  • Power supply: 19 to 28 Vdc
    Static input current: 100 mA


CNC232422485
 
 
 
 

Isolated analog input card, TEA8A

Brochure 128 kb  

  • Function: Converting the 8 analog inputs to digital values and sending them through the serial port.
  • Inputs: 8 type 4 - 20 mA
    Resolution 11 bits plus sign
  • Communications:
    serial port RS485
  • Power supply: 19 a 28 Vdc
    Power consumption: 100 mA

 

MUXFO

 
 
 
 
 

Analog output card , TSA4

Brochure 229 kb  
 

 

MUXFO

  • Function: Convert digital values recibed from CPU into analog current values.
  • Outputs: 4 type loop current control, 4 - 20 mA
    Resolution 16 bits
  • Communications:
    Serial port RS485
    Protocol BUS485
  • Power supply: 9 to 28 Vdc
    Consumption: 200 mA
 
 
 
 
 

Analog input card for PT100, TPT8

Brochure 85 kb  
 

 

MUXFO

  • Function: Converting the 8 PT100 temperature signals to digital values and sending these values through the serial port.
  • Inputs: 8 type Pt100
    Resolution: 0.1ºC
  • Communications:
    Serial port RS485
  • Power supply: 18 to 30 Vdc
    Power consumption: 125 mA @ 24 Vdc
 
 

CONTROLES S.A.